Parameters
Group 15: ANALOG OUTPUTS
This group defines the drive’s analog (current signal) outputs. The drive’s analog
outputs can be:
• any parameter in Group 01: OPERATING DATA
• limited to programmable minimum and maximum values of output current
• scaled (and/or inverted) by defining the minimum and maximum values of the
source parameter (or content). Defining a maximum value (parameter 1503 or
1509) that is less than the content minimum value (parameter 1502 or 1508)
results in an inverted output.
• filtered.
Group 15: Analog Outputs
Code Description Range Resolution Default S
1501 AO1 CONTENT SEL 99…178 1 103 (
OUTPUT FREQ)
Defines the content for analog output AO1.
99 = EXCITE PTC – Provides a current source for sensor type PTC. Output = 1.6 mA. See Group 35: MOTOR TEMP
MEAS.
100 = EXCITE PT100 – Provides a current source for sensor type PT100. Output = 9.1 mA. See Group 35: MOTOR
TEMP MEAS.
101…178 – Output corresponds to a parameter in Group 01: OPERATING DATA.
• Parameter defined by value (value 102 = parameter 0102)
1502 AO1 CONTENT MIN Depends on selection - 0.0 Hz
Sets the minimum content value.
• Content is the parameter selected by parameter 1501.
• Minimum value refers to the minimum content value that will
be converted to an analog output.
• These parameters (content and current min. and max.
settings) provide scale and offset adjustment for the output.
See the figure.
1503 AO1 CONTENT MAX Depends on selection - 60.0 Hz
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will be converted to an analog output.
1504 MINIMUM AO1 0.0…20.0 mA 0.1 mA 4.0 mA
Sets the minimum output current.
AO (mA)
AO CONTENT
P 1504 /
P 1502 / 1508
P 1503 / 1509
AO (mA)
AO CONTENT
P 1505 /
P 1504 /
P 1503 / 1509
P 1502 / 1508
P 1505 /
P 1511
P 1510
P 1511
P 1510