Options
2
Motor type Nominal mains
voltage (U
N
)
Motor insulation requirement
ABB M2 and
M3 motors
U
N
≤ 500 V Standard insulation system.
ABB form-
wound HXR
and AM motors
380 V < U
N
≤ 500 V Standard insulation system.
ABB random-
wound HXR
and AM motors
380 V < U
N
≤ 500 V Check motor insulation system with
the motor manufacturer.
Non-ABB
Random-
wound and
form-wound
U
N
≤ 420 V If the insulation system withstands
Û
LL
=1600 V and Δt=0.2 μs, du/dt
ltering is not required. With du/dt
ltering the insulation system must
withstand Û
LL
=1300 V.
Symbol Explanation
U
N
Nominal mains voltage.
Û
LL
Peak line to line voltage at motor terminals.
Δt Rise time, i.e. interval during which line to line voltage at
motor terminals changes from 10% to 90% of full voltage
range.
du/dt lter type (3 lters included in kits marked *)
Unprotected (IP00)
NOCH0016-60
NOCH0030-60
NOCH0070-60
* NOCH0120-60
* NOCH0260-60
FOCH0260-70
FOCH0320-50
FOCH0610-70
500V
ACS850-04-03A0-5
ACS850-04-03A6-5
ACS850-04-04A8-5
ACS850-04-06A0-5 1
ACS850-04-08A0-5
ACS850-04-010A-5
ACS850-04-014A-5
ACS850-04-018A-5
ACS850-04-025A-5
ACS850-04-030A-5 1
ACS850-04-035A-5
ACS850-04-044A-5
ACS850-04-050A-5
ACS850-04-061A-5 1
ACS850-04-078A-5
ACS850-04-094A-5
ACS850-04-103A-5
ACS850-04-144A-5 1
ACS850-04-166A-5
ACS850-04-202A-5 1
ACS850-04-225A-5
ACS850-04-260A-5 1
ACS850-04-290A-5
ACS850-04-430A-5 1
ACS850-04-521A-5
ACS850-04-602A-5
ACS850-04-693A-5 1
ACS850-04-720A-5
du/dt lter Height
in
Width
in
Depth
in
Weight
lb
NOCH0016-60 7.7 5.5 4.5 5.28
NOCH0030-60 8.5 6.5 5.1 10.34
NOCH0070-60 10.3 7.1 5.9 20.9
NOCH0120-60* 7.9 6.1 4.2 15.4
NOCH0260-60* 15.1 7.3 4.4 26.4
FOCH0260-70 15.0 7.5 10.0 103.4
FOCH0320-50 26.1 12.6 11.1 143
FOCH0610-70 26.1 12.6 11.1 143
Options
du/dt lters
Du/dt ltering suppresses inverter output voltage spikes and
rapid voltage changes that stress motor insulation.
Additionally, du/dt ltering reduces capacitive leakage
currents and high frequency emission of the motor cable
as well as high frequency losses and bearing currents in the
motor.
The need for du/dt ltering depends on the motor age and
insulation. For information on the construction of the motor
insulation, consult the motor manufacturer. If the motor does
not full the requirements of the lter selection table, the
lifetime of the motor might decrease. Insulated N-end (non-
driven end) bearings and/or common mode lters are also
required for motor bearing currents with motors bigger than
100 kW. For more information please see the ACS850 hardware
manual.
Filter selection table for ACS850
External du/dt lters Dimensions and weights of the du/dt lters
* 3 lters included, dimensions apply for one lter.
Mains chokes
Mains chokes are typically used to reduce harmonics in the
mains current.
Frames C to G are equipped with built-in choke as standard.
For frames A and B, the ACS850 drive modules do not
necessarily need a separate mains choke for operation. If
however separate mains choke are needed they are available
to meet different system design needs.