7
Product series
1
Mains connection
Supply voltage 3-phase 380 to 500 V +10 /- 15%
Frequency 50 to 60 Hz ± 5%
DC connection
DC voltage level 485 to 675 V DC ± 10%
Charging Internal
Motor connection
Motor types Induction motors and permanent magnet
motors
Output frequency 0 to 500 Hz
Motor cable length
A&B frames 150 m (with 2nd env. Filter 100 m)
C-G frames: 300 m (with 2nd env. Filter 100 m)
Motor control ABB´s Direct Torque Control
Torque control:
Open loop
Closed loop
Open loop
Closed loop
Speed control:
Open loop
Closed loop
Open loop
Closed loop
Torque step rise time:
<5ms with nominal torque
<5ms with nominal torque
Non-linearity:
±4% with nominal torque
±3% with nominal torque
Static accuracy:
10% of motor slip
0.01% of nominal speed
Dynamic accuracy
0.3 to 0.4%sec. with 100% torque step
0.1 to 0.2%sec. with 100% torque step
Braking power connection
Braking chopper Standard in frames A to D, built-in option in
the other frame sizes
Braking resistor External resistor connected to drive
Operating conditions
Degree of protection IP20 as per EN 60529 (G frame IP00);
Open type as per UL 508.
Ambient temperature -10 to +55 °C (G frame +50 °C), derating
above 40 °C
No frost allowed
Installation altitude 0 to 4000 m (IT network: 2000 m), derating
above 1000 m: 1% / 100 m
Relative humidity max. 95%, no condensation allowed
Climatic/
environmental
conditions
Class 3K3, 3C2 acc. to EN 60721-3-3.
Oil mist, formation of ice, moisture
condensation, water drops, water spray,
water splashes and water jets are not
permissible (EN 60204, Part 1)
Vibration Class 3M4 as per EN 60721-3-3
EMC (According to
EN 61800-3)
Categories C2 and C3 with optional lter
Functional safety (STO acc. EN 61800-5-2)
IEC 61508: SIL 3
EN 954-1: Category 4
IEC 62061: SILCL 3
EN ISO 13849-1: PL e
Certied by TÜV
Compliance Frames A - D: CE, GOST R, UL, cUL;
pending: CSA, C-Tick
Frames E0 - G: CE, GOST R; pending: UL,
cUL, CSA, C-Tick
Shown with optional control panel (+J400)
Technical specications