12 ABB industrial drives ACS880 single drives | Catalog
Standard interface and extensions for comprehensive
connectivity
The ACS880-01 offers a wide range of standard interfaces. In
addition the drive has three option slots that can be used for
extensions including fieldbus adapter modules, input/output
extension modules, feedback modules and a safety functions
module.
Control
connections
Description
2 analog inputs
(XAI)
Current input: –20 to 20 mA,
R
in
: 100 ohm
Voltage input: –10 to 10 V,
R
in
: 200 kohm
Resolution: 11 bit + sign bit
2 analog
outputs (XAO)
0 to 20 mA, R
load
< 500 ohm
Frequency range: 0 to 300 Hz
Resolution: 11 bit + sign bit
6 digital inputs
(XDI)
Input type: NPN/PNP (DI1 to DI5), NPN (DI6)
DI6 (XDI:6) can alternatively be used as an
input for 1 to 3 PTC thermistors.
Digital input
interlock (DIIL)
Input type: NPN/PNP
2 digital
inputs/outputs
(XDIO)
As input:
24 V logic levels:
“0” < 5 V, “1” > 15 V
R
in
: 2.0 kohm
Filtering: 0.25 ms
As output:
Total output current from 24 V DC is limited to
200 mA
Can be set as pulse train input and output
3 relay outputs
XRO1, XRO2,
XRO3
250 V AC / 30 V DC, 2 A
Safe torque-off
(STO)
For the drive to start, both connections must
be closed
Drive-to-drive
link (XD2D)
Physical layer: EIA-485
Built-in
Modbus
EIA-485
Assistant
control panel/
PC tool
connection
Connector: RJ-45
Fault
Default input/output connection diagram
XPOW External power input
1
+24VI
24 V DC, 2 A
2 GND
XAI Reference voltage and analog inputs
1 +VREF
10 V DC, R
L
1 to 10 kohm
2 -VREF
-10 V DC, R
L
1 to 10 kohm
3 AGND Ground
4 AI1+
Speed reference 0(2) to 10 V,
R
in
> 200 kohm
5 AI1-
6 AI2+ By default not in use. 0(4) to 20 mA,
R
in
> 100 ohm
7 AI2-
J1 J1 AI1 current/voltage selection jumper
J2 J2 AI2 current/voltage selection jumper
XAO Analog outputs
1 AO1
Motor speed rpm 0 to 20 mA,
R
L
< 500 ohm
2 AGND
3 AO2
Motor current 0 to 20 mA, R
L
< 500 ohm
4 AGND
XD2D Drive-to-drive link or Modbus
1B
Drive-to-drive link2A
3 BGND
J3 J3 Drive-to-drive link termination switch
XRO1, XRO2, XRO3 Relay outputs
1NC
Ready
250 V AC / 30 V DC
2 A
2 COM
3NO
1NC
Running
250 V AC / 30 V DC
2 A
2 COM
3NO
1NC
Faulted(-1)
250 V AC / 30 V DC
2 A
2 COM
3NO
XD24 Auxiliary voltage output, digital input interlock
1 DIIL By default not in use.
2 +24VD +24 V DC 200 mA
3 DICOM Digital input ground
4 +24VD +24 V DC 200 mA
5 DIOGND Digital input/output ground
J6 Ground selection switch
XDIO Digital inputs/outputs
1 DIO1 Output: Ready
2 DIO2 Output: Running
XDI Digital inputs
1 DI1 Stop (0) / Start (1)
2 DI2 Forward (0) / Reverse (1)
3 DI3 Reset
4 DI4 Acceleration and deceleration select
5 DI5 Constant speed select
6 DI6 By default not in use.
XSTO Safe torque-off
1 OUT1
Safe torque-off. Both circuits must be closed
for the drive to start.
2 SGND
3 IN1
4 IN2
X12 Safety functions module connection
X13 Control panel connection
X205 Memory unit connection