Quick start-up guide
21
Example Configuration: ODVA Basic Speed Control on ACS350
1
The ODVA AC/DC Drive Profile does not provide a means to
supply a RUN ENABLE signal via DeviceNet. The RUN ENABLE
for the drive must either be set to either NOT SEL or another
source (e.g. a digital input).
2 OUTPUT NUM PARS and INPUT NUM PARS should always be
set to 10, except as provided for in the Appendix.
Drive parameter Example setting for ACS350
11.01 EXT1 COMMANDS COMM
11.03 REF1 SELECT COMM
16.01 RUN ENABLE NOT SEL
1
16.04 FAULT RESET SEL COMM
98.02 COMM PROT SEL EXT FBA
51.01 FBA TYPE DEVICENET
51.02 MAC ID 2
51.03 BAUD RATE 0 (= 125 kbit/s)
51.04 RESERVED 0
51.05 ODVA STOP FUNC 0 (=Ramp Stop)
51.06 OUTPUT INSTANCE 20 (=ODVA Basic Speed Control)
51.07 OUTPUT NUM PARS 10
2
51.08 INPUT INSTANCE 70 (=ODVA Basic Speed Control)
51.09 INPUT NUM PARS 10
2
51.10 ODVA SPEED SCALE 128 (= 1 RPM)
51.11 ODVA TORQUE SCALE 128 (= 1 Nm)
51.27 FBA PAR REFRESH REFRESH