Quick start-up guide
25
ABB DRIVES communication profile with PPO Type 2
Drive parameter Example setting for ACS350
1001 EXT1 COMMANDS COMM
1103 REF1 SELECT COMM
1601 RUN ENABLE COMM
1604 FAULT RESET SEL COMM
9802 COMM PROT SEL EXT FBA
5101 FBA TYPE PROFIBUS DP*
5102 NODE ADDRESS 4
5103 BAUDRATE 1500*
5104 PPO TYPE PPO2*
5105 PROFILE 1 (= ABB DRIVES)
5127 FBA PAR REFRESH REFRESH
5401 DATA IN 1 4 (Status word)**
5402 DATA IN 2 5 (Actual value 1)**
5403 DATA IN 3 106 (POWER)**
5404 DATA IN 4 107 (DC BUS VOLTAGE)**
• • •
5501 DATA OUT 1 1 (Control word)**
5502 DATA OUT 2 2 (REF1)**
5503 DATA OUT 3 2501 (CRIT SPEED SEL)**
5504 DATA OUT 4 2502 (CRIT SPEED 1 LO)**
5505 DATA OUT 5 2503 (CRIT SPEED 1 HI)**
• • •
*Read-only or automatically detected
**Example