Drive configuration
35
3 BAUD RATE
This parameter indicates the detected communication speed in
kbit/s.
4 TELEGRAM TYPE
This parameter indicates the selected telegram type for the
PROFIBUS communication. The FPBA-01 automatically detects
the telegram type used, and supports both PPO messages 1 to 6
and standard telegrams (STD) 1 and 20. See Figure 14 in the
chapter Communication for the supported PPO message types.
5 PROFILE
This parameter is used to select which communication profile is
used. The FPBA-01 supports the PROFIdrive, ABB Drives,
Transparent 16 and Transparent 32 profiles.
More information on the communication profiles can be found in
the chapter Communication profiles.
6 T16 SCALE
Reference multiplier/actual value divisor for the FPBA-01. The
parameter is effective only when the Transparent 16 profile is
selected AND the drive is using the DCU communication profile.
For example, a reference of 1,000 given by the PLC will be
multiplied by the value of this parameter, so it will be forwarded to
the drive as 100,000. According to the DCU profile, this value is
interpreted as a reference of 100 rpm.
12000 = 12 Mbit/s
6000 = 6 Mbit/s
3000 = 3 Mbit/s
1500 = 1.5 Mbit/s
500 = 500 kbit/s
187 = 187.5 kbit/s
93 = 93.75 kbit/s
45 = 45.45 kbit/s
19 = 19.2 kbit/s
9= 9.6kbit/s