Communication profiles
48
7 RESET 0 ⇒ 1 Fault reset if an active fault exists. Proceed to SWITCH-
ON INHIBIT.
Note: This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0 (Continue normal operation)
8 INCHING_1 Inching 1. (Not supported by all drive types)
9 INCHING_2 Inching 2. (Not supported by all drive types)
10 REMOTE_
CMD
1 Fieldbus control enabled.
0 Control Word <> 0 or Reference <> 0: Retain last Control
Word and Reference.
Control Word = 0 and Reference = 0: Fieldbus control
enabled.
11 Vendor-specific bit as defined by PROFIdrive parameter
933.
12 Vendor-specific bit as defined by PROFIdrive parameter
934.
13 Vendor-specific bit as defined by PROFIdrive parameter
935.
14 Vendor-specific bit as defined by PROFIdrive parameter
936.
15 Vendor-specific bit as defined by PROFIdrive parameter
937.
Bit Name Value Proceed to STATE/Description