Drive configuration
38
Table 6. FPBA-01 configuration parameters – Group 3
1 DATA IN 1
This parameter represents data word 1 sent by the drive over the
PROFIBUS network. For the contents, see configuration
parameter group 3, parameter 1 (DATA OUT 1) on page 37.
2 to 10 DATA IN 2 to DATA IN 10
See parameter 1 above.
Par.
no.
Parameter name Alternative settings Default
setting
1 DATA IN 1*
(drive to master)
0 to 9999
Format: xxyy, where
xx = parameter group and
yy = parameter index.
4 (Status word)
2 DATA IN 2* See DATA IN 1 above. 5
(Actual value 1)
3 DATA IN 3 See DATA IN 1 above. 0
4 DATA IN 4 See DATA IN 1 above. 0
5 DATA IN 5 See DATA IN 1 above. 0
6 DATA IN 6 See DATA IN 1 above. 0
7 DATA IN 7 See DATA IN 1 above. 0
8 DATA IN 8 See DATA IN 1 above. 0
9 DATA IN 9 See DATA IN 1 above. 0
10 DATA IN 10 See DATA IN 1 above. 0
*These can be modified only in Transparent 16 and Transparent 32 modes
(see FPBA-01 configuration parameters – Group 1).