Drive configuration
34
Table 4. FPBA-01 configuration parameters – Group 1
Note: Set also the extended Parameter Data (see SAP 61 in the
chapter Communication) to ensure proper operation of the
FPBA-01 with the drive.
1 FBA TYPE
This parameter shows the fieldbus adapter type as detected by
the drive. The value cannot be adjusted by the user.
If this parameter is undefined, the communication between the
drive and the module has not been established.
2 NODE ADDRESS
Each device on the PROFIBUS network must have a unique node
number. This parameter is used to define a node number for the
drive it is connected to.
Par.
no.
Parameter name Alternative settings Default
setting
1 FBA TYPE (Read-only) PROFIBUS DP
2 NODE ADDRESS 0 to 126 3
3 BAUD RATE* (12000) 12 Mbit/s; (6000) 6 Mbit/s;
(3000) 3 Mbit/s; (1500) 1.5 Mbit/s;
(500) 500 kbit/s; (187) 187.5 kbit/s;
(93) 93.75 kbit/s; (45) 45.45 kbit/s;
(19) 19.2 kbit/s; (9) 9.6 kbit/s
1500
4 TELEGRAM TYPE* (1) PPO 1; (2) PPO 2; (3) PPO 3;
(4) PPO 4; (5) PPO 5; (6) PPO 6;
(7) STD1; (8) STD20
(Read-only)
(1) PPO 1
5PROFILE (0) PROFIdrive; (1) ABB Drives;
(2) Transparent 16;
(3) Transparent 32
(1) ABB Drives
6 T16 SCALE 1 to 65535 100
*The value is automatically updated (Read-only).