ACH550-01 User's Manual
Application macros and wiring 109
1 SCR Signal cable shield (screen)
2 AI1 Not used
3 AGND Analogue input circuit common
4 10V Reference voltage +10 V DC
5 AI2 Not used
6 AGND Analogue input circuit common
7AO1Output frequency: 0(4)…20 mA
8AO2Output current: 0(4)…20 mA
9 AGND Analogue output circuit common
10 24V Auxiliary voltage output +24 V DC
11 GND Common for DI return signals
12 DCOM Digital input common for all
13 DI1 Start/Stop: Activation starts the drive in the timer mode
14 DI2 Run enable: Deactivation stops the drive
1
15 DI3 Boost: Momentary activation starts the boost function
16 DI4 Start enable 1: Deactivation stops the drive
1
17 DI5 Start enable 2: Deactivation stops the drive
1
18 DI6 Not used
19 RO1C Relay output 1 (par. 1401)
Default operation
Started => 19 connected to 21
20 RO1A
21 RO1B
22 RO2C Relay output 2 (par. 1402)
Default operation
Running => 22 connected to 24
23 RO2A
24 RO2B
25 RO3C Relay output 3 (par. 1403)
Default operation
Fault (-1) => 25 connected to 27
26 RO3A
27 RO3B
1
Disable/enable with parameters 1601, 1608 and 1609
Note: The drive starts only if possible protection functions (Run enable or Start enable 1 and
2) are activated from I/O or disabled with parameters.
Internal timer with constant speeds