ABB RCNA-01 Manual de usuario Pagina 378

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 474
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 377
374 Diagnostics and maintenance
ACH550-01 User's Manual
Fault resetting
The ACH550 can be configured to automatically reset certain
faults. Refer to parameter Group 31: AUTOMATIC RESET.
WARNING! If an external source, e.g. AUTO key, is selected for
start command and it is active, the ACH550 may start
immediately after fault reset.
Flashing red LED
To reset the drive for faults indicated by a flashing red LED:
Turn off the power for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not
flashing), correct the problem and do one of the following:
From the control panel: press RESET.
Turn the power off for 5 minutes.
Depending on the value of 1604 FAULT RESET SEL the following
could also be used to reset the drive:
digital input
serial communication.
When the fault has been corrected, the motor can be started.
Vista de pagina 377
1 2 ... 373 374 375 376 377 378 379 380 381 382 383 ... 473 474

Comentarios a estos manuales

Sin comentarios