190 Parameter listing and descriptions
ACH550-01 User's Manual
-7 = DI1,2(INV) – Selects one of three constant speeds (1…3) using DI1
and
DI2.
• Inverse operation uses two digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI activated):
-8 =
DI2,3(INV) – Selects one of three constant speeds (1…3) using DI2
and
DI3.
• See above (
DI1,2(INV)) for code.
-9 =
DI3,4(INV) – Selects one of three constant speeds (1…3) using DI3
and
DI4.
• See above (
DI1,2(INV)) for code.
-10 =
DI4,5(INV) – Selects one of three constant speeds (1…3) using DI4
and
DI5.
• See above (
DI1,2(INV)) for code.
-11 =
DI5,6(INV) – Selects one of three constant speeds (1…3) using DI5
and
DI6.
• See above (
DI1,2(INV)) for code.
-12 =
DI1,2,3(INV) – Selects one of seven constant speeds (1…7) using
DI1, DI2 and DI3.
• Inverse operation uses three digital inputs, as defined below (0 =
DI
de-activated, 1 =
DI activated):
-13 =
DI3,4,5(INV) – Selects one of seven constant speeds (1…7) using
DI3, DI4 and DI5.
• See above (
DI1,2,3(INV)) for code.
-14 =
DI4,5,6(INV) – Selects one of seven constant speeds (1…7) using
DI4, DI5 and DI6.
• See above (
DI1,2,3(INV)) for code.
Code Description Range
DI1 DI2 Function
1 1 No constant speed
0 1 Constant speed 1 (1202)
1 0 Constant speed 2 (1203)
0 0 Constant speed 3 (1204)
DI1 DI2 DI3 Function
1 1 1 No constant speed
0 1 1 Constant speed 1 (1202)
1 0 1 Constant speed 2 (1203)
0 0 1 Constant speed 3 (1204)
1 1 0 Constant speed 4 (1205)
0 1 0 Constant speed 5 (1206)
1 0 0 Constant speed 6 (1207)
0 0 0 Constant speed 7 (1208)