288 Parameter listing and descriptions
ACH550-01 User's Manual
Group 51: EXT COMM MODULE
This group defines set-up variables for an external fieldbus
communication module. Refer to the communication module
documentation for more information on these parameters.
Code Description Range
5101 FBA TYPE
Displays the type of the connected fieldbus adapter module.
0 =
NOT DEFINED – Module not found or not connected. Check chapter
Mechanical installation in the fieldbus user’s manual and check that
parameter 9802 is set to 4 = EXT FBA.
1 =
Profibus-DP
21 = LonWorks
32 = CANopen
37 = DeviceNet
101 = ControlNet
128 = Ethernet
132 = PROFINET
136 = EPL - Ethernet POWERLINK
144 = CC-Link
5102
5126
FB PAR 2…FB PAR 26 0…65535
Refer to the communication module documentation for more
information on these parameters.
5127 FBA PAR REFRESH 0=DONE, 1=REFRESH
Validates any changed fieldbus parameter settings.
0 =
DONE – Refreshing done.
1 =
REFRESH – Refreshing.
After refreshing, the value reverts automatically to
DONE.
5128 FILE CPI FW REV 0…0xFFFF
Displays the CPI firmware revision of the drive’s fieldbus adapter
configuration file. Format is xyz, where:
x = major revision number
y = minor revision number
z = correction number.
Example: 107 = revision 1.07
5129 FILE CONFIG ID 0…0xFFFF
Displays the revision of the drive’s fieldbus adapter module’s
configuration file identification.
File configuration information depends on the drive application
program.
5130 FILE CONFIG REV 0…0xFFFF
Contains the revision of the drive’s fieldbus adapter module
configuration file.
Example: 1 = revision 1