334 Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
123456
15 ANALOGUE
AO1
CONTENT
SEL 1501
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUT
FREQ
OUTPUTS
AO1
CONTENT
MIN 1502 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
AO1
CONTENT
MAX 1503 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz
MINIMUM AO1 1504 4.0 mA 4.0 mA 4.0 mA 4.0 mA 4.0 mA 4.0 mA
MAXIMUM
AO1
1505 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA
FILTER AO1 1506 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s
AO2
CONTENT
SEL 1507 CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
AO2
CONTENT
MIN 1508 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A 0.0 A
AO2
CONTENT
MAX 1509
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
Defined by
par. 0104
MINIMUM AO2 1510 4.0 mA 4.0 mA 4.0 mA 4.0 mA 4.0 mA 4.0 mA
MAXIMUM
AO2
1511 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA
FILTER AO2 1512 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s
16 SYSTEM RUN ENABLE 1601 NOT SEL DI2 DI2 DI2 DI2 DI2
CONTROLS
PARAMETER
LOCK
1602 OPEN OPEN OPEN OPEN OPEN OPEN
PASS CODE 1603 0 0 0 0 0 0
FAULT RESET
SEL
1604 KEYPAD KEYPAD KEYPAD KEYPAD KEYPAD KEYPAD
USER PAR
SET CHG
1605 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
LOCAL LOCK 1606 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
PARAM SAVE 1607 DONE DONE DONE DONE DONE DONE
START
ENABLE 1
1608 DI4 DI4 DI4 DI4 DI4 DI4
START
ENABLE 2
1609 NOT SEL DI5 DI5 DI5 DI5 DI5
DISPLAY
ALARMS
1610 NO NO NO NO NO NO
PARAMETER
VIEW
1611 DEFAULT DEFAULT DEFAULT DEFAULT DEFAULT DEFAULT