4010 SET POINT SEL 0…20
Defines the reference signal source for the PID controller.
• Parameter has no significance when the PID regulator is by-passed
(see 8121
REG BYPASS CTRL).
0 =
KEYPAD – Control panel provides reference.
1 =
AI1 – Analogue input 1 provides reference.
2 =
AI2 – Analogue input 2 provides reference.
8 =
COMM – Fieldbus provides reference.
9 =
COMM+AI1 – Defines a fieldbus and analogue input 1 (AI1)
combination as the reference source. See Analogue input reference
correction on page 276.
10 =
COMM
*
AI1 – Defines a fieldbus and analogue input 1 (AI1)
combination as the reference source. See Analogue input reference
correction on page 276.
11 =
DI3U,4D(RNC) – Digital inputs, acting as a motor potentiometer
control, provide reference.
•
DI3 increases the speed (the U stands for “up”)
•
DI4 decreases the reference (the D stands for “down”).
• Parameter 2205
ACCELER TIME 2 controls the reference signal’s rate
of change.
•
R = Stop command resets the reference to zero.
•
NC = Reference value is not copied.
12 =
DI3U,4D(NC) – Same as DI3U,4D(RNC) above, except:
• Stop command does not reset reference to zero. At restart the motor
ramps up, at the selected acceleration rate, to the stored reference.
13 =
DI5U,6D(NC) – Same as DI3U,4D(NC) above, except:
• Uses digital inputs
DI5 and DI6.
14 =
AI1+AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 276.
15 =
AI1
*
AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 276.
16 =
AI1-AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 276.
17 =
AI1/AI2 – Defines an analogue input 1 (AI1) and analogue input 2
(
AI2) combination as the reference source. See Analogue input
reference correction on page 276.
19 =
INTERNAL – A constant value set using parameter 4011 provides
reference.
20 =
PID2OUT – Defines PID controller 2 output (parameter 0127 PID 2
OUTPUT) as the reference source.