ABB RCNA-01 Manual de usuario Pagina 317

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 474
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 316
Parameter listing and descriptions 313
ACH550-01 User's Manual
2 = DI2 – Enables the Interlock function, and assigns a digital input
(starting with
DI2) to the interlock signal for each PFA relay. These
assignments are defined in the following table and depend on:
• the number of PFA relays [number of parameters 1401…1403 and
1410…1412 with value = 31 (PFA)]
the Autochange function status (disabled if 8118
AUTOCHNG INTERV =
0.0, and otherwise enabled).
Code Description Range
No. PFA
relays
Autochange disabled
(P 8118)
Autochange enabled
(P 8118)
0
DI1: Free
DI2: Speed Reg Motor
DI3…DI6: Free
Not allowed
1
DI1: Free
DI
2: Speed Reg Motor
DI3: First PFA Relay
DI4…DI6: Free
DI1: Free
DI
2: First PFA Relay
DI3…DI6: Free
2
DI1: Free
DI2: Speed Reg Motor
DI3: First PFA Relay
DI4: Second PFA Relay
DI5…DI6: Free
DI1: Free
DI2: First PFA Relay
DI3: Second PFA Relay
DI4…DI6: Free
3
DI1: Free
DI2: Speed Reg Motor
DI3: First PFA Relay
DI4: Second PFA Relay
DI5: Third PFA Relay
DI6: Free
DI1: Free
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5…DI6: Free
4
DI1: Free
DI2: Speed Reg Motor
DI3: First PFA Relay
DI4: Second PFA Relay
DI5: Third PFA Relay
DI6: Fourth PFA Relay
DI1: Free
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5: Fourth PFA Relay
DI6: Free
5 Not allowed
DI1: Free
DI2: First PFA Relay
DI3: Second PFA Relay
DI4: Third PFA Relay
DI5: Fourth PFA Relay
DI6: Fifth PFA Relay
6 Not allowed Not allowed
Vista de pagina 316
1 2 ... 312 313 314 315 316 317 318 319 320 321 322 ... 473 474

Comentarios a estos manuales

Sin comentarios