262 Parameter listing and descriptions
ACH550-01 User's Manual
3615 STOP TIME 4
Defines timer 4 daily start time.
See parameter 3603.
3616 START DAY 4
Defines timer 4 weekly start day.
See parameter 3604.
3617 STOP DAY 4
Defines timer 4 weekly stop day.
See parameter 3605.
3622 BOOST SEL -6…6
Selects the source for the boost signal.
0 =
NOT SEL – Boost signal is disabled.
1 =
DI1 – Defines DI1 as the boost signal.
2…6 =
DI2…DI6 – Defines DI2…DI6 as the boost signal.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the boost signal.
-2…-6 = Defines an inverted digital input
DI2…DI6 as the boost signal.
3623 BOOST TIME 00:00:00…23:59:58
Defines the boost ON time. Time is started when
BOOST SEL signal is
released. If parameter value is 01:30:00, boost is active for 1 hour and
30 minutes after activation DI is released.
Code Description Range
Boost active
Activation DI
Boost time