376 Diagnostics and maintenance
ACH550-01 User's Manual
2003 UNDERVOLTAGE The undervoltage controller is active. Check for
and correct:
undervoltage on mains.
2004
DIR LOCK The change in direction being attempted is not
allowed. Either:
do not attempt to change the direction of motor
rotation, or
change parameter 1003
DIRECTION to allow
direction change (if reverse operation is safe).
2005
IO COMM Fieldbus communication has timed out. Check for
and correct:
fault setup (3018
COMM FAULT FUNC and 3019
COMM FAULT TIME)
communication settings (Group 51: EXT COMM
MODULE or Group 53: EFB PROTOCOL as
appropriate)
poor connections and/or noise on line.
2006
AI1 LOSS Analogue input 1 is lost, or value is less than the
minimum setting. Check:
input source and connections
parameter that sets the minimum (3021)
parameter that sets the alarm/fault operation
(3001).
2007
AI2 LOSS Analogue input 2 is lost, or value is less than the
minimum setting. Check:
input source and connections
parameter that sets the minimum (3022)
parameter that sets the alarm/fault operation
(3001).
Alarm
code
Display Description